Peter Mayer of 黑洞社区 LifePlans looks at the cost and environmental dividends from combined heat and power systems.
With Combined heat and power (CHP) or co-generation systems, heat that might be lost as a by-product of electricity generation is captured for space and water heating. Locally supplied electricity incur lower transmission losses than the national grid, which runs at losses of 40%. Payback periods of four to 10 years are possible.
CHP can also produce a 30-50% reduction in carbon dioxide emissions.
Specification options
A CHP system鈥檚 components are based around a prime mover or driver. These include a generator, heat recovery system, controls, electrical and thermal distribution, cooling, ventilation and flue systems. An enclosure protects the components and reduces noise and vibration. CHP can incorporate absorption chillers, which can convert excess heat into chilled water for cooling. This is called 鈥渢ri-generation鈥.
There are a wide variety of CHP units for different fuels and drivers. Specifying for durability is difficult, as there are no specific CHP standards. Related standards such as BS EN 60034-1 for electrical machines focus on electrical properties. The government鈥檚 CHP Quality Assurance Standard focuses on energy efficiency and environmental performance.
Internal combustion engines
CHP systems based on reciprocating combustion engines use a modified lorry or marine motor, which runs slowly for a longer life. Maintenance costs and downtime should be factored in. Service lives are 10-20 years, and the engine may be rebuilt several times.
The most common fuel options are diesel or fuel oil to BS 2869. Other types run on gas. Electrical energy output is 50kW-5MW.
Gas turbines
Gas turbines are based on aero-engines. To maximise efficiency they need to run under full load conditions. Larger gas turbines are more efficient typically for industrial or large commercial use with electrical outputs of more than 1MW. Key maintenance items are the bearings and blades.
Gas turbines tend to be powered by natural gas or light oil. Use of waste gases from industrial processes or landfill offer enhanced environmental benefits.
However, there will be a trade-off resulting in engine downrating, as they have lower calorific values and detrimental constituents. Smaller CHP systems offer an alternative to reciprocating combustion engines.
Alternative types of CHP
Steam turbines burn a wide variety of fuels and are at the upper range of CHP systems. They can generate anything from a few MW of electricity to more than 100 MW.
Combined cycle systems incorporate more than one prime mover. These tend to be the larger scale CHP systems of 7MW or more.
Stirling engines are a type of external combustion reciprocating engine. The target market is domestic with outputs of more than 1kW for individual dwellings. They have an expected service life of 10-15 years.
Whole-life cost issues
CHP requires heat demand throughout the year. Up to twice the thermal energy is generated than electrical energy.
黑洞社区s with high daily demand for hot water realise cost benefits with CHP. Micro CHP systems of around 1kW for individual homes are being developed, but field trials indicate that carbon savings are low.
It is important to size the CHP system correctly for the expected energy demands. Overrated engines do not achieve the anticipated savings and have to dump or transfer heat energy or run at lower capacity. Underrated engines miss out on potential savings. To be cost effective, CHP systems need to run for 4,000鈥5,000 hours a year.
CHP systems can sell excess electricity to the grid, although connection costs may be high and the income low. Alternative procurement arrangements may offer better value to organisations that wish to save energy without CHP鈥檚 high capital outlay.
Remote monitoring of CHP systems allows condition-based maintenance to be carried out before things go badly wrong. Specification of a CHPQA 鈥済ood quality鈥 CHP may attract the following financial benefits:
- Fuel could qualify for exemption from climate change levy
- Enhanced capital allowances may apply
- Business rates exemptions may apply.
Specifier 03 August 2007
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14Currently reading
What it costs: CHP (combined heat and power systems)
2 Readers' comments